CE3300MS-10.5-> BACK
Functional Excellence
// The most advanced ADEC electronic management system
// The most advanced Common-rail Electrical Injection system统
// The most advanced emission control
// Optimal fuel efficiency, high reliability and availability
// Long repair/maintenance period
// Small size, powerful and stable with long service life
// In compliance with ISO8528, GB/T2820, NFPA110
// Certified in CE, TLC, ABP
// Meets TA-Luft, Singapore ORDE NEA, US EPA standard
-
Industry-leading load system
Backup power with load factor as 80%
-
Manufactured and designed in compliance with ISO
Certification of ISO 9001:2015、ISO 14001:2015 and OHSAS18001:2015
-
Advanced monitoring and communication system
A great variety of application including Genset Island Mode and Grid-connected mode, detailed monitoring picture, PLC parameters, multi languages and varied ways of communication
Technical data
Diesel Genset
-
Type CE3300MS-10.5
- Frequency 50HZ
-
Voltage 10500V
- Power factor 0.8(lagging)
- Connection 3-phase and 3-wire
- Start method 24VDC start
-
Continuous Power N/A
-
Standby Power 2640/3300(KW/KVA)
-
Dimension (L*W*H) 12192*3200*3200mm
-
Weight 31680kg
Diesel Engine
-
Brand MTU
-
Type 20V4000G63L
- Rated speed 1500rpm
-
Bore * Stroke 170*210mm
- No. of Cylinders and arrangement 20V
-
Displacement 95.4L
-
Compression ratio 16.4:1
- Aspiration Turbocharging
- Speed Control Mode Electrical/ADEC
-
Fuel Injection Common-rail Electrical Injection
- Cooling Radiator Water Tank
- Oil Capacity 390L
-
Coolant Capacity 690L
Alternator
- Brand LeroySomer
-
Type LSA53.2 ZL14
-
Rated Power 2240/2800 (KW/KVA)
-
Excitation Mode AREP (PMG as the option)
- Protection Grade IP23
- Insulation Grade Class H
- Rated Temperature Rise 105℃
Control System
- Brand DEIF
- Model CGC413
- √ Remote Monitoring
- √ Incident Record
- √ Multiple Languages
- √ Remote Self-starting
- √ Auto Detection of Mains Failure
- √ Multi-contact Input/Output
- √ Comprehensive System Protection
- (Optional: Parallel operation of multiple gensets,Synchronization with mains)
Note: The specifications are subject to change without notice.